| Technical Specification | SUN2000-100KTL-M1 |
| Efficiency | |
| Max. Efficiency | 98.8% @480 V; 98.6% @380 V/400 V |
| European Efficiency | 98.6% @480 V; 98.4% @380 V/400 V |
| Input | |
| Max. Input Voltage | 1,100 V |
| Max. Current per MPPT | 26A |
| Max. Short Circuit Current per MPPT | 40A |
| Start Voltage | 200V |
| MPPT Operating Voltage Range | 200 V ~ 1,000 V |
| Rated Input Voltage | 570 V @380 V; 600 V @400 V; 720 V @480 V |
| Number of Inputs | 20 |
| Number of MPP Trackers | 10 |
| Output | |
| Rated AC Active Power | 100,000 W (380 V / 400 V / 480 V @40°C) |
| Max. AC Apparent Power | 110,000 VA |
| Max. AC Active Power (cosφ=1) | 110,000 W |
| Rated Output Voltage | 220 V / 230 V, default 3W + N + PE; 380 V / 400 V / 480 V, 3W + PE |
| Rated AC Grid Frequency | 50 Hz / 60 Hz |
| Rated Output Current | 152.0 A @380 V; 144.4 A @400 V; 120.3 A @480 V |
| Max. Output Current | 168.8 A @380 V; 160.4 A @400 V; 133.7 A @480 V |
| Adjustable Power Factor Range | 0.8 LG ... 0.8 LD |
| Max. Total Harmonic Distortion | <3% |
| Protection | |
| Input-side Disconnection Device | Yes |
| Anti-islanding Protection | Yes |
| AC Overcurrent Protection | Yes |
| DC Reverse-polarity Protection | Yes |
| PV-array String Fault Monitoring | Yes |
| DC Surge Arrester | Type II |
| DC Insulation Resistance Detection | Yes |
| Residual Current Monitoring Unit | Yes |
| General Data | |
| Dimensions (W x H x D) | 1,035 x 700 x 365mm (40.7 x 27.6x 14.4 inch) |
| Weight (with mounting plate) | 90 kg (187.4 lb.) |
| Operating Temperature Range | -25°C ~ 60°C (-13°F ~ 140°F) |
| Cooling Method | Smart Air Cooling |
| Max. Operating Altitude | 4,000 m (13,123 ft.) |
| Relative Humidity | 0 ~ 100% |
| DC Connector | Staubli MC4 |
| AC Connector | Waterproof Connector + OT/DT Terminal |
| Protection Degree | IP66 |
| Topology | Transformerless |
| Night Time Power Consumption | ≤ 3.5 W |